FAQs

FAQ Search
Most Recently Published FAQs

Results 61 - 70 of 100

FAQ ID Description
FA22653Is it possible to use the current Limiter LA9LB920 or GV1L3 with Tesys GV3 range of MPCB to increase the breaking capacity.
LA9LB920 and GV1L3 current limiter are dedicated to Tesys GV2 Motor Protection Circuit Breaker (MPCB) product range and can be used with MPCB rated...
FA135921Why even after the registration key validation; every time while launching the software, a small window is appearing and asking for the registration.
User can just click "OK" and go for the next screen to work on My Ecodial L.(if the software evaluation period is over; then the OK button will...
FA12217Can TeSys range overload relays be used in DC application.
The overload relay with the bimetal technology (Thermal Overload) only can be used in DC application. Tesys LRD RangeTesys LRD thermal overload relays...
FA12216What is the maximum number of sensors and resistance values which can be connected to the T1 and T2 terminals on TeSys T.
You can wire maximum 6 sensors (PTC or NTC analog) to Temperature Input terminals T1 and T2 on TeSys T.And, you can go up to a maximum of 6500 ohms...
FA12208What is the maximum DC voltage per pole for TeSys F Range contactors.
The maximum DC voltage for TeSys F range contactors is 125 Volt per pole. This voltage is applicable for the specification of L/R
FA12194What is the short circuit current rating for TeSys GV2G Comb Busbar.
The short-circuit current withstand rating (KA) of Tesys Comb Busbar is compatible with the breaking capacity of Motor Protection Circuit Breakers...
FA12190Is it possible to use LTME DC Expansion module with LTMR AC module of TeSys T.
Yes, it is possible to use LTME DC Expansion module with LTMR AC module of TeSys T.
FA12178What is the maximum cable length allowed between PC and TeSys T for connection via PowerSuite.
The maximum cable length allowed between PC and TeSys T connection via PowerSuite depends on the system and the converter used.If the standard converter,...
FA22772What is the difference between 31088 and 31097 key locking devices.
31097 keylocking device is used for the Single Handle Source Changeover Assembly in which different type off cam is used. These cams are to be ordered...
FA22774What are the characteristics of STR13MAE (MAE500) trip unit used in Compact NS630 circuit breaker.
The Compact NS630 fitted with the STR13MAE trip unit is named: NS630MAE500.   The old MA500 trip unit was designed with mechanical feature. The new...