| FA22653 | Is it possible to use the current Limiter LA9LB920 or GV1L3 with Tesys GV3 range of MPCB to increase the breaking capacity. LA9LB920 and GV1L3 current limiter are dedicated to Tesys GV2 Motor Protection Circuit Breaker (MPCB) product range and can be used with MPCB rated... |
| FA135921 | Why even after the registration key validation; every time while launching the software, a small window is appearing and asking for the registration.
User can just click "OK" and go for the next screen to work on My Ecodial L.(if the software evaluation period is
over; then the OK button will... |
| FA12217 | Can TeSys range overload relays be used in DC application. The overload relay with the bimetal technology (Thermal Overload) only can be used in DC application. Tesys LRD RangeTesys LRD thermal overload relays... |
| FA12216 | What is the maximum number of sensors and resistance values which can be connected to the T1 and T2 terminals on TeSys T. You can wire maximum 6 sensors (PTC or NTC analog) to Temperature Input terminals T1 and T2 on TeSys T.And, you can go up to a maximum of 6500 ohms... |
| FA12208 | What is the maximum DC voltage per pole for TeSys F Range contactors. The maximum DC voltage for TeSys F range contactors is 125 Volt per pole. This voltage is applicable for the specification of L/R |
| FA12194 | What is the short circuit current rating for TeSys GV2G Comb Busbar. The short-circuit current withstand rating (KA) of Tesys Comb Busbar is compatible with the breaking capacity of Motor Protection Circuit Breakers... |
| FA12190 | Is it possible to use LTME DC Expansion module with LTMR AC module of TeSys T. Yes, it is possible to use LTME DC Expansion module with LTMR AC module of TeSys T. |
| FA12178 | What is the maximum cable length allowed between PC and TeSys T for connection via PowerSuite. The maximum cable length allowed between PC and TeSys T connection via PowerSuite depends on the system and the converter used.If the standard converter,... |
| FA22772 | What is the difference between 31088 and 31097 key locking devices. 31097 keylocking device is used for the Single Handle Source Changeover Assembly in which different type off cam is used. These cams are to be ordered... |
| FA22774 | What are the characteristics of STR13MAE (MAE500) trip unit used in Compact NS630 circuit breaker. The Compact NS630 fitted with the STR13MAE trip unit is named: NS630MAE500.
The old MA500 trip unit was designed with mechanical feature. The new... |